Air-cooled prefabricated cabin energy storagebattery system is a large-capacitybattery energy storage devicewith standardized design and flexible configuration.
This product integrates energy storage battery,BMS,convergence cabinet,temperaturecontrol system and fire protection system,and can be used with mainstreamenergystorage converters for various energy storage application scenarios.
The new generation 5MWh air-cooledproductadopts adistributed airconditioning solution with excellent temperature control performance and makingt particularly suitable forcold and high-altitude environments.
The highly integrated structural design of theproduct can significanty save land andshorten theconstructionperiodfor users.
Model | THESS-500-1003 | THESS-630-1290 | THESS-1000-2007 | THESS-1260-2150 |
AC (Grid tied) | ||||
Apparent Power | 550kVA | 693kVA | 1100kVA | 1280kVA |
Rated Power | 500kW | 630kW | 1000kW | 1200kW |
Rated Voltage | 400V | |||
Rated Current | 722A | 909A | 1444A | 1563A |
Voltage Range | 360V ~ 440V | |||
Frequency | 50/60Hz | |||
THDI | <3% | |||
Power Factor | - 0.9 leading ~ 0.9 lagging | |||
Wire Connection | 3 / N / PE | |||
AC input | 550kVA | 693kVA | 1100kVA | 1280kVA |
AC (Off-grid) | ||||
Apparent Power | 550kVA | 693kVA | 1100kVA | 1280kVA |
Rated Power | 500kW | 630kW | 1000kW | 1200kW |
Rated Voltage | 400V | |||
Rated Current | 722A | 909A | 1444A | 1563A |
THDU | ≤2% | |||
Frequency | 50/60Hz | |||
Overload Capability | 110% for long-term; 120% for 1min | |||
DC (Battery and PV) | ||||
Max. PV Open-circuit Voltage | 1000V DC | |||
Rated PV Power | 500kWp | 600kWp | 1000kWp | 1000kWp |
Max. PV Power | 1.1~1.4 times rated | |||
PV Voltage Range | 400V ~ 600V DC | |||
Max. PV Current | 100A×10 | 100A×12 | 100A×20 | 100A×20 |
PV MPPT NO. | 10 | 12 | 20 | 20 |
Battery Voltage Range | 627V ~ 850V | |||
Available Battery Capacity | 1003.52kWh 1505.28kWh 2007.04kWh | 1290.24kWh 1935.36kWh | 2007.04kWh | 2150.4kWh |
Max. Charge Power | 500kW | 630kW | 1000kW | 1200kW |
Max. Discharge Power | 500kW | 630kW | 1000kW | 1200kW |
Max. Charge Current | 722A | 909A | 1444A | 1540A |
Max. Discharge Curretn | 722A | 909A | 1444A | 1540A |
Basic Parameters | ||
Noise Level | <65dB(A)@1m | |
IP protection level | IP54 | |
Fire protection | C6F12O fire extinguisher | |
Operating Temperature | -25℃ ~ +55℃ | |
Protection Function | Over /under voltage, Over current, Over/low temperature, SOC too high/low Low insulation impedance, Short circuit protection, etc | |
Cooling | Forced air + Smart AC | |
Relative Humidity | 0 ~ 95%, non-condensing | |
Max. Altitude | 4000m ( >2000m derating capacity ) | |
Dimensions(W×D×H) | 6058×2438×2896mm 12192×2438×2896mm | |
Weight | 25T(20 feet) 38T(40 feet) | |
Build-in Transformer | Optional | |
Communication | ||
HMI | Touch Screen | |
Communication | RS485 / CAN / LAN |