01
01

Eos

Categories:
Distribution Network C&I BESS
Tag:
C&I BESS Distribution Network Micro-grid

In the Eos commercial energystorage system,long-ife battery cells,new BMS control methods,high-performancePCS,intellienttemperature control system,and active fire control system are integrated into the standardized outdoor cabinets.Eosis designed withthe concept of completely independent electrical and battery components spaces,to enhance thereliability of system temperaturecontrol and fire safety protection.The product is applied in various aplicationscenarios,such as peak cut,new energy consumption,dynamic expansion,and low voltage control of power grid.

DataSheet
Parameters

Model

TESS-30-100

TESS-50-100

TESS-100-215

TESS-120-241

AC (on-grid)

Apparent power

33kVA

55kVA

110kVA

132kVA

Rated power

30kW

50kW

100kW

120kW

Rated voltage

400V

Rated current

43A

72A

144A

173A

Voltage range

360V ~ 440V

Rated frequency

50/60HZ

THDI

<3%

Power factor

-0.9 lead ~ 0.9 lag

Wire Connection

3/N/PE

AC input

33kVA

55kVA

110kVA

132kVA

AC (off-grid)

Apparent power

33kVA

55kVA

110kVA

132kVA

Rated power

30kW

50kW

100kW

120kW

Rated voltage

400V

Rated current

43A

72A

144A

173A

THDU

≤2%

Rated frequency

50/60HZ

Overload capacity

110%for long-term;120%for Imin

DC (battery & PV)

Max. PV open-circuit voltage

700V DC

Rated PVPower

30kWp

50kWp

100kWp

100kWp

Max.PV Power

1.1-1.4times rated

PV Voltage Range

400V ~ 700V DC

Max.PV Current

60A

100A

100A X2

100A X2

MPPT NO.

1

1

2

2

Battery Voltage Range

324V~397V

324V~397V

696V~852V

696V~852V

Available Battery Capacity

100.35kWh

100.35kWh

215.04kWh

241.92kWh

Max.Charge Power

30kW

50kW

100kWh

120kWh

Max. discharge power

30kW

50kW

100kW

120kW

Max. charge current

92A

154A

143A

172A

Max. discharge current

92A

154A

143A

172A

Basic Parameters

On/off grid switch function

Assorting

On/off grid switch time

≤10ms

Noise Level

<65dB(A)@1m

IP protection level

IP54

Fire protection

Aerosols

Operating Temperature

-25℃-+55℃

Protection Function

Over /under voltage,Over current,Over/low temperature,SOC too high/lowLowinsulation impedance,Short circuit protection,ete

Cooling

Forced air+SmartAC

Relative Humidity

0~95%,without condensation

Max.Altitude

4000m(>2000m derating)

Dimensions(WxDxH)

1000×1000×2350mm

1000×1000×2350mm

1545×1000×2350mm

1545×1000×2350mm

Communication

Display

Touch Screen

Communication interface

RS485 / CAN

More