The system is a power supply system integrating energy storage converter,high and lowvoltage distribution equipment,step-up transformer and station power supply system,which can support 6~35kV grid access and meet the application of large or super large energy storage power plant.
Model | TBVS-1000K-T | TBVS-1260K-T |
DC side parameters | ||
Maximum DCvoltage | 1000vdc | |
DCvoltage range | 600Vdc~850Vdc | |
Maximum DC curren | 1852A | 2332A |
Automatic pre-charge function | Equipped | |
AC(grid-connected)parameters | ||
Rated Power | 1000kw | 1260kw |
Maximum power | 1100kw | 1386kw |
Maximum current | 1588A | 2000A |
Ratedgrid-connected voltage | 400Vac | |
Allowable Voltage Range | 400Vac士10% | |
Frequency range | 50/60Hz土5Hz | |
Power Factor /Adjustable Range | - 0.99(Overrun)~0.99(lagging) | |
THDI | ≤3% | |
AC(off-grid)parameters | ||
RatedVoltage | 400Vac | |
VoltageAccuracy | 1% | |
Maximum current | 1588A | 2000A |
Output Frequency | 50/60Hz土5Hz | |
THDU | ≤3% | |
Efficiency | - | |
Maximum efficiency | 99% | |
Transformer Characteristics | ||
Rated Power | 1000kw | 1260kw |
Voltage Ratio | 0.4/6~35kV | |
Transformer Type | Oil change /dry change | |
Basic Features | ||
Protection Grade | IP54 | |
Operating Temperature | -15℃-50℃ | |
Relative humidity | ≤95%RH,non-condensing | |
Cooling method | Air cooling | |
Weight | About 1200kg | |
Altitude | 4000m(more than 2000m reduction) | |
Human-computer interaction | Touch Screen | |
Noise | ≤65dB | |
Communication mode | Ethernet.RS485、4G | |
Outline Dimensions | 6058mmx2896mmx2438mm |